SPECIFICATION FOR WIRE & CABLES COVERED UNDER IS : 694 (1990) CONSTRUCTION OF CONDUCTOR
NOMINAL CROSS SECTIONAL AREA
COPPER
Up to and including 6 mm2
Above 6 Mm2
ALUMINUM
Up to and including 6 mm2
Above 6 Mm2
SOLID / STRANDED FLEXIBLITY CLASS
Solid/Standard Class 1 or Class 2 of IS : 8130/1984
Stranded Class 2 of IS : 8130/1984
SINGLE CORE PVC INSULATED UNSHEATHED CABLES
Nominal Cross Sectional area of Conductor (mm2)
Nominal Cross Thickness of insulation (mm)
Overall Diameter Maximum (mm)
Nominal Cross Sectional area of Conductor (mm2)
Nominal Thickness of Insulation (mm)
Overall Diameter Maximum (mm)
1*
0.7
3.2
50
1.4
13
1.5
0.7
3.4
70
1.4
15
2.5
0.8
4.2
95
1.6
17.5
4
0.8
4.8
120
1.6
19
6
0.8
5.6
150
1.8
21
10
1
7
185
2
23
16
1
8.2
240
2.2
26.5
25
1.2
10
300
2.4
29.5
35
1.2
11.5
400
2.6
33.5
500
2.8
37.5
600
2.8
42
* For Copper Conditions Only
PVC INSULATED SHEATHED CABLE
Nominal Cross
Senctional
Area of Conductor
Nominal Thickness
of insulation
Nominal Thickness Of Sheath Overall Dimensions
Overall Dimensions
Single core
Twin core
Three core
Four core
Single core
Twin core circular
Twin
Flat
Three circular
Four circular
mm2
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
1*
0.6
0.8
0.9
0.9
0.9
4.7
8.2
7.8´5.0
8.6
9.2
1.5
0.6
0.8
0.9
0.9
0.9
5
8.8
8.4´5.4
9.2
10
2.5
0.7
0.8
1
1
1
5.8
10.5
10´6.4
11
12
4
0.8
0.9
1
1.1
1.1
6.8
12
11.5´7.2
13
14
6
0.8
0.9
1.1
1.1
1.2
7.8
13.5
13.0´8.0
14.5
15.5
10
1
0.9
1.2
1.2
1.3
8.8
16.5
16.0´9.6
17.5
19.5
16
1
1
1.3
1.3
1.4
10.5
19
18.5´11.0
20
22.5
25
1.2
1.1
1.5
1.5
1.6
12.5
23
22.0´13.0
24.5
27.5
35
1.2
1.1
1.6
1.6
1.7
13.5
25.5
25.´14.5
27.5
30.5
50
1.4
1.2
1.7
1.7
1.8
15.5
29.5
29.0´16.5
31.5
35
* For Copper Conditions Only
SINGLE CORE, UNSHEATHED CABLE IN VOLTAGE GRADE 1100V
Nominal are of Conductor
Number/Nom Dia of Wire
Number/Nom Dia of Wire
Aprox Overall Diameter
Current carrying capacity# 2 cables, single phase
Resistance(Max.) per km. @ 20oC
Ohms.
In conduit/Trunking (Amps.)
Unenclosed clipped directly to a surface or on cable tray (Amps.)
0.75
24/2*
0.6
2.4
7
1
14/.3*
0.7
2.8
11
12
18.1
1.5
22/.3*
0.7
3.1
13
16
12.1
4.5
36/.3*
0.8
3.8
18
22
7.41
4
56/.3*
0.8
4.4
24
29
4.95
6
84/.3*
0.8
5.2
31
37
3.3
Standard Colour : Black, Red, Blue and Green (fcr earthing) Supplied in 90 Meter
length in attractive packaging # A Per IS : 3961 (Part –V) – 1968 *As
per conductor Class 2 of IS : 8130/1984
CURRENT CARRYING CAPACITY The Current rating given in the tables are based on the following
assumptions.
a) Maximum Conductor Temperature
-
70o C
b) Thermal Resistivity of Soil
-
150o C cm/w
c) Thermal Resistivity of PVC
-
650o C cm/w
d) Ground Temperature
-
30o C
e) Ambient Air Temperature
-
40o C
f) Depth of Laying (to the highest point of the cable laid direct in round or to
the top surface of ducts)